4-channel measuring bridge analysis, full/half/quarter bridge, 24 bit, 10 ksps, with external calibration certificate ELM3504-0030
XFC – eXtreme Fast Control
calibration certificate
measuring bridges

ELM3504-0030 | 4-channel measuring bridge analysis, full/half/quarter bridge, 24 bit, 10 ksps, with external calibration certificate

The ELM350x EtherCAT Terminals are designed for the evaluation of measuring bridges in full-bridge, half-bridge and quarter-bridge configuration. The terminals feature internally switchable supplementary resistors. The feed is integrated. Like all other parameters, the supply voltage is adjustable in the CoE. Irrespective of the signal configuration, all ELM modules have the same technological properties. The ELM350x modules for the evaluation of measuring bridges offer a maximum sampling rate of 10,000 or 20,000 samples per second. The 6-pin plug (push-in) can be removed for maintenance purposes without releasing the individual wires.

For the ELM350x-0030, an individual calibration certificate is available, currently as a choice of DAkkS or IS0 17025-compliant certificate. The certificate is issued by an accredited service provider in collaboration with Beckhoff. The desired calibration certificate can be downloaded from www.beckhoff.com/certificates using the respective serial number.

Features ELM350x
Strain gauge quarter bridge (350 Ω + 120 Ω), half bridge (up to ±16 mV/V), full bridge (up to ±32 mV/V), internal bridge completion and supply adjustable 0…5 V (2-/3-/4-/5-/6-wire connection), shunt calibration
Voltage measurement ±10 V, ±80 mV, 0…10 V
Potentiometer measurement potentiometer ≥ 1 kΩ, supply integrated and adjustable 0…5 V
Temperature measurement (RTD) PT1000
Technical data ELM3504-0030
Number of channels 4
Technology resistor bridge, strain gauge
Signal type differential
Connection technology 2-/3-/4-/5-/6-wire
Connection type push-in, service plug 6-pin
Max. sampling rate max. 100 µs/10 ksps (per channel, simultaneously)
Oversampling factor n = 1…100 selectable (max. 10 ksamples/s)
Internal resistance > 4 MΩ
Measuring error up to typ. < ±500 ppm/0.05 % relative to the respective full scale value
Temperature coefficient up to < 10 ppm/K typ.
Functional diagnostics yes
Connection diagnostics broken wire/short circuit
Distributed clocks yes, accuracy << 1 µs
Resolution 24 bit (incl. sign)
Current consumption power contacts
Current consumption E-bus typ. 720 mA
Weight approx. 350 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Thermal dissipation typ. 3 W
Special features ExtendedRange 107 %, free numeric filter, TrueRMS, integrator/differentiator, non-linear scaling, PeakHold, calibrated version of ELM3504-0000
Approvals/markings CE, UL
Accessories  
ZS9100-0002 shield connection for ELM series, shield diameter 7…16 mm
ZS9100-0003 shielding hood for EtherCAT measurement modules with push-in connector (ELM3xxx-0000), to provide shielding against external interference and temperature stabilisation at the measuring points when measuring temperature, black, scope of supply: shielding hood, screws, tie wraps